Standard Operating Procedure- Diesel Generator
Starting procedure for Diesel Generators in "AUTO" mode
|
Keep both the Emergency Stop switches in AMF panel and Generator panel released condition
|
In AMF panel keep the Selector switch in "Auto" mode of all DG set
|
In Generator panel keep the key switch in "AUTO" mode
|
Ensure the Lube oil level with in the allowable limit.
|
Check day tank diesel level (above 80%)
|
Keep the radiator water upto the Brim
|
Check the battery condition
|
If Transformer-1&2,only TFR # 1,or TFR # 2 incomer breaker goes "Off" or if power fails D.G will start automatically
|
Ensure DG Outgoing # 1 and 2 ACB for Close,if open close manually
|
Check D.G Output Voltage,load current,Frequency,Water Temp.,Lube oil Pressure,Battery Voltage and Day tank diesel level every 15 minutes once and record in once in a hour
|
Stopping procedure for Diesel Generators "AUTO" mode.
|
Ensure the EB supply voltage is with in the limit (400V to 440V)
|
Check and ensure that protective relays (Over current,Earth fault,Earth Leakage Over/Under Voltage etc) are in normal mode, reset if required
|
Ensure that Trip circuit healthy lamp indication is glowing
|
changer over will happen from Emergency supply to Normal supply
|
Now D.G load transferred to EB. D.G breaker goes off automatically
|
Starting procedure for Diesel Generators in "Manual" mode
|
Keep both the Emergency Stop switches in AMF panel and Generator panel released condition
|
Ensure the Lube oil level with in the allowable limit.
|
Check day tank diesel level (above 80%)
|
Keep the radiator water upto the Brim
|
Check the battery condition
|
Switch On the DG #1 and DG#2 manually.
|
Ensure all parameters of DG in limit and close the DG breakers and MV panel output breakers in DG AMF panel
|
Check D.G Output Voltage,load current,Frequency,Water Temp.,Lube oil Pressure,Battery Voltage and Day tank diesel level every 15 minutes once and record in once in a hour
|
Stopping procedure for Diesel Generators in "Manual" mode
|
Take the necessary readings
|
Ensure the EB Supply voltage is with in the limit
|
Check and ensure that protective relays (Over current,Earth fault,Earth Leakage Over/Under Voltage etc) are in normal mode, reset if required
|
Ensure that Trip circuit healthy lamp indication is glowing
|
Ensure the changover happen automaticaly in ATS panel
|
After 3 minutes switch OFF the DG by pressing stop button
|
Check the diesel level in the day tank,add diesel if needed
|