Standard Operating Procedure- Transformer
Switching "ON" of Transformer
|
Check and ensure the protective relays (Over current,Earth fault,Earth Leakage Over/Under Voltage etc) are in normal mode, reset if required
|
Check and ensure exhaust fans are in working condition.
|
Close the HT VCB of required transformer by pressing the ON push button on the respective VCB
|
Observe the nosie level of Transformer for normal working condition. Check for any abnormal noise from Transformer, if found switch OFF the Transformer by following switching off procedure
|
Close the respective LT ACB on the Main LT panel by pressing ON push button
|
Record HT and LT parameters like Voltage, current, Transformer Winding Temperature etc.
|
Switching "OFF" of Transformer
|
Trip the respective LT ACB in the Main LT panel by pressing the OFF push button
|
Trip the respective HT VCB in the HT breaker panel by pressing the OFF push button
|
Ensure the VCB is in open through "OPEN" indicator installed in the HT Breaker panel and measurement of voltage on LT side.
|