Standard Operating Procedure- Capacitior Panel
Switch "ON" feeder (Auto Operation)
|
In the Panel keep the Selector switch for all capacitor bank in auto mode
|
Check the indicators R,Y and B are glowing on respective feeder of capacitor bank feeder
|
Check panel doors are closed switched ON main Incomer Breaker
|
Check and ensure that protective relays (Over current, Over/Under Voltage etc) are in normal mode.
|
Ensure that OFF indication lamp is glowing
|
Ensure that rubber mats infront of panel is in place
|
Turn/push the control switch/Start push button for "On" position . The ON indication lamp will also glow
|
ensure Off Indication is not glowing
|
Switch "ON" feeder (Auto Operation)
|
Turn/push the control switch/stop push button for "OFF" position . The OFF indication lamp will also glow
|
Switched off Main Incomer
|