Performance Check list-Half Yearly | | | | | | |
Ensure that no leakage current is present in the transformer after discharging | | | | | |
Check cable glands | | | | | | |
Check for sign of overheating or deterioration on the LT/HT terminals | | | | | | |
Check bushing of the transformer for any crack | | | | | | |
Check abnormal noise. If any from the transformer. | | | | | | |
Check the winding and Oil temperature trip setting of the transformer and check oil guage pointer for freedom | | | | |
Check oil level in the transformer and test oil for acidity and sludge. Arrange oil filteration/topping as required | | | | |
Check for any poor contacts on the tap changer of the winding | | | | | | |
Check the operation of the air circulation fan of the transformer , if any | | | | | | |
Inspect whether the neutral terminal of the transformer connected to earth seperately or not | | | | |
Carry out the earth resistance measurement of the transformer neutral and water it if required | | | | |
Tighten all earth terminals | | | | | | |
Check alarm circuits , clean contacts if any. | | | | | | |
Inspect Buchholtz relay and its operation | | | | | | |
Check for the proper installation of the safeties and remove Tag out | | | | | | |
After switching On the mains , observe the voltage, current readings and record it. | | | | | |
Verify test results and plan correction , if required.
Performance Check list-Yearly |
Ensure that no leakage current is present in the transformer after discharging |
Check cable glands |
Check for sign of overheating or deterioration on the LT/HT terminals |
Check bushing of the transformer for any crack |
Check abnormal noise. If any from the transformer. |
Check the winding and Oil temperature trip setting of the transformer and check oil guage pointer for freedom |
Check oil level in the transformer and test oil for acidity and sludge. Arrange oil filteration/topping as required |
Check for any poor contacts on the tap changer of the winding |
Check the operation of the air circulation fan of the transformer , if any |
Inspect whether the neutral terminal of the transformer connected to earth seperately or not |
Carry out the earth resistance measurement of the transformer neutral and water it if required |
Tighten all earth terminals |
Check alarm circuits , clean contacts if any. |
Inspect Buchholtz relay and its operation |
Check for the proper installation of the safeties and remove Tag out |
After switching On the mains , observe the voltage, current readings and record it. |
Verify test results and plan correction , if required. |
| | | | | | |
Keep your projects collaborated by i2e consulting which provides great services like project and portfolio management with best practices and methodologies that helps an increase in growth of business organizations to cut their implementation costs while maintaining high quality delivery. For More details http://i2econsulting.com/services/project-management-solution/