Domestic Pump | ||||||
Ensure standby pumps are in opeartion, if required | ||||||
Apply Lock In & tag Out notice | ||||||
Performance Check list | ||||||
Inspect condition of shaft seal and for any leaks | ||||||
If shaft seal is leaking, disconnect coupling and replace mechanical seal or repack seal | ||||||
Check mechanical coupling | ||||||
Lubricate motor and pump bearings | ||||||
Check operating pressures from guage , if any , to ensure clean strainer. Clean pump strainer | ||||||
Check tightness of foundation bolt | ||||||
Remove cover of motor terminal box and check the termination and for any overheating | ||||||
Check for any loose connection and tighten it properly | ||||||
Check running load curent for all three phases | ||||||